Evco S.p.A. • Code 104K261E00
EVK261 Digital thermostat for normal temperature refrigerated transport, with compressor or instrument working days counter function version 1.00
GB ENGLISH
1 GETTING STARTED
1.1 Important
Read these instructions carefully before installing and using the instru-
ment and follow all additional information for installation and electrical
connection; keep these instructions close to the instrument for future
consultations.
The instrument must be disposed according to the local
legislation about the collection for electrical and electronic
equipment.
1.2 Installing the instrument
Panel mounting, with click brackets (supplied by the builder); dimen-
sions in mm (in).
DIMENS. MINIMUM TYPICAL MAXIMUM
A 71.0 (2.795) 71.0 (2.795) 71.8 (2.826)
B 29.0 (1.141) 29.0 (1.141) 29.8 (1.173)
Additional information for installation:
59.0 (2.322) is the maximum depth with screw terminal blocks
83.0 (3.267) is the maximum depth with extractable terminal blocks
the panel thickness must not be higher than 8.0 mm (0.314 in)
working conditions (working temperature, humidity, etc.) must be be-
tween the limits indicated in the technical data
do not install the instrument close to heating sources (heaters, hot air
ducts, etc.), devices provided with big magnetos (big speakers, etc.),
locations subject to direct sunlight, rain, humidity, dust, mechanical
vibrations or bumps
according to the safety legislation, the protection against electrical
parts must be ensured by a correct installation of the instrument; the
parts that ensure the protection must be installed so that you can not
remove them if not by using a tool.
1.3 Wiring diagram
With reference to the wiring diagrams:
terminals 1 and 2 are available only in the models with power supply
230 VAC and 115 VAC; terminals 8 and 9 are available only in the
models with power supply 12 VAC/DC and 12-24 VAC/DC
the function of the second input depends on parameter P4
port 1 (by request) is the serial port for the communication with the
supervision system (through a serial interface, via TTL, with MODBUS
communication protocol) or with the programming key; the port must
not be used at the same time for the same purposes
port 2 (by request) is the port for the communication with the remote
indicator; the indicator shows the quantity you have set with param-
eter P5.
Additional information for electrical connection:
• do not operate on the term. blocks with electrical or pneumatic screwers
if the instrument has been moved from a cold location to a warm one,
the humidity could condense on the inside; wait about an hour be-
fore supplying it
test the working power supply voltage, working electrical frequency
and working electrical power of the instrument; they must correspond
with the local power supply
disconnect the local power supply before servicing the instrument
do not use the instrument as safety device
for repairs and information on the instrument please contact Evco
sales network.
2 USER INTERFACE
2.1 Preliminary information
There are the following operation status:
status “on” (the instrument is supplied and is turned on: the regulators
can be turned on)
status “stand-by” (the instrument is supplied but it is turned off via
software: the regulators are turned off)
status “off” (the instrument is not supplied).
If parameter t0 has value 0, “turning on” means moving from status off
to status on; “turning off” means moving from status on to status off.
If parameter t0 has value 1, “turning on” means moving from status
stand-by to status on; “turning off” means moving from status on to
status stand-by.
After an interruption of power supply the instrument moves to the sta-
tus it was before the interruption.
2.2 Turning on/off the instrument if parameter t0 has
value 0
To turn on the instrument you have to supply it; to turn it off it is enough
to cut off the power supply.
2.3 Turning on/off the instrument if parameter t0 has
value 1
make sure the keyboard is not locked and no procedure is running
press 4 s.
2.4 The display
If the instrument is turned on, during the normal operation the display
will show the quantity you have set with parameter P5:
if P5 = 0, the display will show the cabinet temperature
if P5 = 1, the display will show the working setpoint
if P5 = 2, the display will show the temperature read by the auxiliary
probe (only if parameter P4 has value 1 or 2).
2.5 Showing the cabinet temperature
make sure the keyboard is not locked and no procedure is running
press 2 s: the display will show the first available label
press or to select “Pb1
press
To quit the procedure:
press or do not operate 60 s
press or as long as the display shows the quantity you have
set with parameter P5 or do not operate 60 s.
2.6 Showing the temperature read by the auxiliary probe
(only if parameter P4 has value 1 or 2)
make sure the keyboard is not locked and no procedure is running
press 2 s: the display will show the first available label
press or to select “Pb2
press
To quit the procedure:
press or do not operate 60 s
press or as long as the display shows the quantity you have
set with parameter P5 or do not operate 60 s.
If the function of the second input is not the one of auxiliary probe
(parameter P4 = 0 or 3), the label “Pb2” will not be shown.
2.7 Activating the defrost by hand
make sure the keyboard is not locked and no procedure is running
press 4 s.
If the function of the second input is the one of evaporator probe (pa-
rameter P4 = 1) and to the defrost activation the evaporator tempera-
ture is above the one you have set with parameter d2, the defrost will
not be activated.
2.8 Locking/unlocking the keyboard
To lock the keyboard:
make sure no procedure is running
press and 2 s: the display will show “Loc” 1 s.
If the keyboard is locked, you will not be allowed to:
turn on/off the instrument by hand
show the temperature read by the auxiliary probe
activate the defrost by hand
modify the working setpoint with the procedure related in paragraph
3.1 (you also can modify the working setpoint through parameter SP)
show the compressor working days
erase the compressor working days
show the instrument working days
erase the instrument working days.
These operations provoke the visualization of the label “Loc” 1 s.
To unlock the keyboard:
press and 2 s: the display will show “UnL” 1 s.
2.9 Silencing the buzzer
make sure no procedure is running
press a button (the first pressure of the button does not provoke its
usual effect).
3 SETTINGS
3.1 Setting the working setpoint
make sure the keyboard is not locked and no procedure is running
press LED will flash
press or in 15 s; also look at parameters r1, r2 and r3
press or do not operate 15 s.
You also can modify the working setpoint through parameter SP.
3.2 Setting configuration parameters
To gain access the procedure:
make sure no procedure is running
press and 4 s: the display will show “PA
press
press or in 15 s to set “-19
press or do not operate 15 s
press and 4 s: the display will show “SP”.
To select a parameter:
press or
To modify a parameter:
press
press or in 15
press or do not operate 15 s.
To quit the procedure:
press and 4 s or do not operate 60 s.
Switch off/on the power supply of the instrument after the
modification of the parameters.
3.3 Restoring the default value of configuration param-
eters
make sure no procedure is running
press and 4 s: the display will show “PA
press
press or in 15 s to set “743
press or do not operate 15 s
press and 4 s: the display will show “dEF
press
press or in 15 s to set “149
press or do not operate 15 s: the display will show “dEF” flash-
ing 4 s, after which the instrument will quit the procedure
switch off/on the power supply of the instrument.
Make sure the default value of the parameters is appropri-
ate.
4 COMPRESSOR OR INSTRUMENT WORKING DAYS
COUNTING
4.1 Preliminary information
The instrument can store up to 1,999 compressor or instrument work-
ing days, after which the number 1,999 flashes.
If parameter t1 has value 0, the instrument will store the compressor
working days; if parameter t1 has value 1, the instrument will count its
working days (also when it is turned off via software).
When the number of working days gets the one you have set with
parameter t2, the display shows the label “SEr” flashing.
To freeze the signal “SEr” 1 h:
press a button (the first pressure of the button does not provoke its
usual effect).
4.2 Showing the working days
make sure the keyboard is not locked and no procedure is running
press 2 s: the display will show the first available label
press or to select “Ct
press the display will show in succession the following informa-
tion (for example):
INFOR. MEANING
dd the display is about to show the working days
26 the working days are 26 (to be continued ...)
hh the display is about to show the working hours
03 the working days are 26 and the hours are 3
Each information lasts 1 s.
To escape from the succession of information:
press
To quit the procedure:
escape from the succession of information
press or as long as the display shows the quantity you have
set with parameter P5 or do not operate 60 s.
4.3 Erasing the working days
make sure the keyboard is not locked and no procedure is running
press 2 s: the display will show the first available label
press or to select “rCt
press
press or in 15 s to set “149
press or do not operate 15 s: the display will show “- - - -” flashing
4 s, after which the instrument will quit the procedure.
5 SIGNALS
5.1 Signals
LED MEANING
LED compressor
if it is lit, the compressor will be turned on
if it flashes:
the modification of the working setpoint will be running
a compressor protection will be running (parameters C0,
C1, C2 and i7)
LED defrost
if it is lit, the defrost will be running
LED alarm
if it is lit, an alarm will be running
°C LED Celsius degree
if it is lit, the unit of measure of the temperatures will be
Celsius degree (parameter P2)
°F LED Fahrenheit degree
if it is lit, the unit of measure of the temperatures will be
Fahrenheit degree (parameter P2)
CODE MEANING
SEr service of compressor or of instrument is requested (param-
eter t2); also look at chapter 4
Loc the keyboard and/or the working setpoint are locked (pa-
rameter r3); also look at paragraph 2.8
- - - - the quantity to show is not available (for example because
the probe is not enabled)
6 ALARMS
6.1 Alarms
CODE MEANING
AL Lower temperature alarm
Remedies:
check the temperature joined to the alarm
look at parameters A0, A1 and A2
Effects:
no effect
AH Upper temperature alarm
Remedies:
check the temperature joined to the alarm
look at parameters A3, A4 and A5
Effects:
no effect
id Door switch input alarm (only if parameter P4 has value 3
and parameter i0 has value 3)
Remedies:
check the reasons that have provoked the activation of
the input
look at parameters i0 and i1
Effects:
the compressor will be turned off
iA Multipurpose input alarm (only if parameter P4 has value 3
and parameter i0 has value 0)
Remedies:
check the reasons that have provoked the activation of
the input
look at parameters i1 and i5
Effects:
if parameter i5 has value 3, there will be no effect
if parameter i5 has value 4, the compressor will be turned
off
iSd Instrument locked alarm (only if parameter P4 has value 3
and parameter i0 has value 0)
Remedies:
check the reasons that have provoked the activation of
the multipurpose input
switch off/on the power supply of the instrument
look at parameters i1, i5, i7, i8 and i9
Effects:
the regulators will be turned off
COH Overheated condenser alarm (only if parameter P4 has value
2)
Remedies:
check the condenser temperature
look at parameter C6
Effects:
no effect
CSd Compressor locked alarm (only if parameter P4 has value 2)
Remedies:
check the condenser temperature
cut off the power supply of the instrument and clean the
condenser
look at parameter C7
Effects:
the compressor will be turned off
When the cause that has provoked the alarm disappears, the instru-
ment restores the normal operation, except for the instrument locked
alarm (code “iSd”) and the compressor locked alarm (code “CSd”) that
need you switch off/on the power supply of the instrument.
7 INTERNAL DIAGNOSTICS
7.1 Internal diagnostics
CODE MEANING
Pr1 Cabinet probe error
Remedies:
look at parameter P0
check the integrity of the probe
check the connection instrument-probe
check the cabinet temperature
Effects:
the compressor activity will depend on parameters C4 and
C5
Pr2 Auxiliary probe error (only if parameter P4 has value 1 or 2)
Remedies:
the same you saw in the previous case but related to the
auxiliary probe
Effects:
if parameter P4 has value 1, the defrost will last the time
you will have set with parameter d3
if parameter P4 has value 1 and parameter d8 has value 2,
the instrument will work as if parameter d8 had value 0
if parameter P4 has value 2, the overheated condenser
alarm (code “COH”) and the compressor locked alarm
(code “CSd”) will never be activated
When the cause that has provoked the alarm disappears, the instru-
ment restores the normal operation.
8 TECHNICAL DATA
8.1 Technical data
Box: self-extinguishing grey.
Frontal protection: IP 65.
Connections: screw terminal blocks (power supply, inputs and out-
put), 6 poles connector (serial port; by request), 4 poles connector (to
the remote indicator; by request); extractable terminal blocks (power
supply, inputs and output) by request.
Working temperature: from 0 to 55 °C (32 to 131 °F, 10 ... 90% of
relative humidity without condensate).
Power supply: 230 VAC, 50/60 Hz, 3 VA (approximate); 115 VAC or
12-24 VAC/DC or 12 VAC/DC by request.
Alarm buzzer: by request.
Measure inputs: 1 (cabinet probe) for PTC/NTC probes.
Digital inputs: 1 (multipurpose/door switch) for NO/NC contact (free
of voltage, 5 V 1 mA) also configurable for measure input (evaporator
or condenser probe, for PTC/NTC probes).
Working range: from -50.0 to 150.0 °C (-50 to 300 °F) for PTC probe,
from -40.0 to 105.0 °C (-40 to 220 °F) for NTC probe.
Resolution: 0.1 °C/1 °C/1 °F.
Digital outputs:1 relay:
compressor relay: 16 res. A @ 250 VAC (change-
over contact).
The maximum current allowed on the load is 10 A.
Serial port: port for the communication with the supervision system
(through a serial interface, via TTL, with MODBUS communication pro-
tocol) or with the programming key; by request.
Further communication ports: port for the communication with
the remote indicator; by request.