EC 3-533E 4/95
CONFIGURATION PARAMETERS
CODE PARAMETER DESCRIPTION MIN MAX U.M. ST
(1) PA PASSWORD -55 +99 ----
/ PROBE
/0 kind of probe 30 = 4-20 mA ; 31 = 0-20 mA 30 3 1 ---- 30
(1) /1 calibration (measure offset) -9.0 +10 bar 0
/2 digital filter (speed response) 0=0s; 1=0.4s; 2=1.2s; 3=3.0s; 4=8.0s; 5=19.8s; 6=48.0s 0 6 ---- 3
/4 without leading zeros 0=NO; 1=YES 0 1 ---- 1
/5 with decimal point 0=NO; 1=YES 0 1 ---- 0
/6 start of scale for input 0-20 mA or 4-20 mA corrispondent to input's minimum value -99 999 bar see table 2
/7 end of scale for input 0-20 mA or 4-20 mA corrispondent to input's maximum value -99 999 bar see table 2
rA PRESSURE REGULATOR
(1) rA0 regulator hysteresis (differential) -99 +999 bar -0.2
rA1 minimum setpoint admitted -99 +999 bar see table 2
rA2 maximum setpoint admitted -99 +999 bar see table 2
rA3 output action 0=active for high pressure (direct); 1=active for low pressure (reverse) 0 1 ---- 1
rA4 hysteresis selection 0=asymmetric; 1=symmetric 0 1 ---- 0
rA5 setpoint adjustement locking 0=unlocked; 1=locked 0 1 ---- 0
CA OUTPUT ACTIVATION DELAY
CA0 output activation delay since instrument power-on 0 999 sec 0
CA1 after start delay 0 999 sec 0
CA2 after stop delay 0 999 sec 0
CA3 relay output status in case of probe failure 0=OFF; 1=ON 0 1 ---- 0
CA4 ON and OFF delay 0=no delay; 1=3sec 0 1 ---- 0
AA/Ab ALARM AA=refered to alarm 1; Ab=refered to alarm 2
AA/Ab0 alarm hysteresis (differential) 1 +99 bar 0
AA/Ab1 alarm setpoint -99 +999 bar 0
AA/Ab3 alarm disabling time since instrument power-on 0 999 min 0
AA/Ab4 alarm mode see table 1 1
L NETWORK CONNECTION
L1 instrument address 1 1 5 ---- 1
L2 instrument group 0 7 ---- 0
TABLE 2
connected range par. /6 par. /7 par. rA1 par. rA2
transducer (bar) (bar) (bar) (bar) (bar)
EC PRS 00 -0.5÷7 -0.5 7 -0.5 7
EC PRS 01 0÷25 0 25 0 25
EC PRS 02 0÷30 0 30 0 30
EC PRS 03 0÷250 0 250 0 250
CUSTOM configurable according to the needs
TABLE 1
parameter AA/Ab4 alarm mode
1 disabled
2 absolute minimum alarm
3 absolute maximum alarm
4 minimum alarm relative to setpoint 1
5 maximum alarm relative to setpoint1
6 minimum alarm relative to setpoint 1
with automatic enabling and recompute
7 maximum allarm relative to setpoint 1
with automatic enabling and recompute
notes
(1) = configuration parameter on LEVEL 1
N.B. On request, it is possible to configure the instrument with different unit of measure.
The transducers pressure ranges are to be considered as " relative to atmospheric pressure ";
the unit of measure is bar (1 bar = 0.1 MPa; 1 MPa = 10 bar).