EVCO S.p.A. c-pro 3 hecto MCSA | User manual ver. 2.0 | Code 144MCSAE204
page 42 of 52
Label Parameter description Default Min Max
INSTALLER PARAMETERS - LINE
PL01
System line type
0: low temperature
1: high temperature
1 0 1
PL02 Low temperature line set-point (summer) 18.0 7.0 30.0
PL03 Low temperature line set-point (winter) 30.0 20.0 90.0
PL04 High temperature line set-point (summer) 12.0 5.0 30.0
PL05 High temperature line set-point (winter) 60.0 25.0 90.0
PL06 Dew point offset 3.0 0.0 10.0
PL10 High temperature set-point 45.0 0.0 90.0
PL11 High temperature differential 5.0 0.0 10.0
PL12 Low temperature set-point 10.0 -10.0 40.0
PL13 Low temperature differential 5.0 0.0 10.0
PL14 Lock high temperature alarm delay (minutes) 2 0 30
PL15
Type of lock high temperature alarm
0 – No
1 – Automatic
2 - Manual
1
0
2
PL16 Lock low temperature alarm delay (minutes) 2 0 30
PL17
Type of lock low temperature alarm
0 – No
1 – Automatic
2 - Manual
1
0
2
PL20
Chiller-hp activation delay from system line pump O
(seconds)
60 0 255
PL21
Regulation for heating/cooling external control
0: Valve lateral band
1: Valve maximum opening
2: Valve minimum opening
2 0 2
PL22
Chiller-hp switch-off delay with active zones request
(minutes)
1 0 30
PL23
Temperature delta for pump switch-off with chiller-hp in alarm
mode
5.0 0 10.0
PL24
Chiller-hp switch-off delay without active zones request
(seconds)
10 0 255
INSTALLER PARAMETERS - PUMP
PP01 Enable pump anti-grip cycle 1 (Yes) 0 (No) 1 (Yes)
PP02 System line pump On delay (seconds) 30 0 255
PP03 System line pump Off delay (seconds) 60 0 255
INSTALLER PARAMETERS - VALVE
PV01 Enable valve anti-grip cycle 1 (Yes) 0 (No) 1 (Yes)
PV02 Valve delay from System line pump ON 30 0 255
PV05 Valve min value 0.0 0.0 100.0
PV06 Valve max value 100.0 0.0 100.0
PV11
Minimum external temperature in Summer mode for
calculation of the shifting set-point
10.0 0.0 30.0