EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104
EVCO
page 12 of 68
3.1.2 I/O Configuration with 1-speed fans with more speed
variator
c-pro 3 hecto + CAN with 2 A/O V+V
I/O Description
Analogue inputs
AI 1 Anti-freeze Temperature Probe (Recovery heat exchanger By-Pass) NTC
AI 2 Not used
AI 3 Not used
AI 4 Not used
AI 5 Not used
AI 6 Not used
AI 7 Not used
AI 8 Not used
AI 9 Not used
Serial ports
RS485 RS485 Modbus RTU
CAN bus To Vgraph
Digital inputs
DI 1 Presence sensor
DI 2 Start – Stop (remote)
DI 3 Supply fan thermal protection
DI 4 Return fan thermal protection
DI 5 Not used
DI 6 Not used
DI 7 Not used
DI 8 Not used
DI 9 Not used
Analogue outputs
AO 1 Not used
AO 2 Not used
AO 3 Recovery heat exchanger BY-PASS damper control (0-10 V) *
AO 4 Return fan control signal (0-10 V)
AO 5 Supply fan control signal (0-10 V)
AO 6 Mixing room damper control (0-10 V)
Digital Outputs (Relay)
DO 1 Return fan (speed 0) enabling
DO 2 Supply fan (speed 0) enabling
DO 3 Not used
DO 4 Not used
DO 5 Not used
DO 6 Not used
DO 7 Recovery heat exchanger BY-PASS damper control *
DO 8 Not used
DO 9 Not used
(*) The recovery heat exchanger BY-PASS damper control can be analogic or digital, and
setting with clock