EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104
EVCO
page 32 of 68
PF10
Differential for the by-pass of the recovery
unit damper in anti-freeze protection
mode
2.0 0.0
20.0
36.0
°C
°F
CO-F
PF11
Fans working time in post-ventilation
mode
30 0 999 Sec CO-F
OUTSIDE AIR DAMPER
This menu is only accessible if PG04=1
PS01
Fans switch-on delay from outside air
damper activation
45 0 999 Sec CO-SE
Reading
only
PS02
Outside air damper switch-OFF delay from
fans switch-off
15 0 999 Sec CO-SE
PS05 Delay of outside air damper end run 60 0 999 Sec CO-SE
PS06
Enable FreeHeating
0: No
1: Yes
No (0) No (0) Yes (1) CO-SE
PS07
Type damper control mixing room
0: Free-Heating only
1: Regulating air quality only
2: Priorities on demand higher of the two
3: Average of the two requests
4: Fixed open
0 0 4 CO-SE
PS08
Minimum aperture shutter
mixing room
20.0 0.0 PS09 % CO-SE
PS09
Maximum aperture shutter mixing
chamber
100.0 PS08 100.0 % CO-SE
PS10 Fixed value of damper opening 50.0 0.0 100.0 % CO-SE
PS12
Differential which enables free-cooling
and free-heating temperature
2.0 0.0 20.0 °C CO-SE
PS13
Setpoint differential which enables free-
cooling and free-heating temperature
4.0 0.0 20.0 °C CO-SE
PS15
Opening the minimum and maximum
damper
0:
Disabled
1: Only internal bandwidth
2: Always
2 0 2 CO-SE
PS20 Setpoint - adjusting the air quality 600 0 10000 ppm CO-SE
PS21 Differential - adjusting the air quality 100 0 2000 ppm CO-SE
RECOVERY HEAT EXCHANGER
Pr01
Anti-freeze temperature minimum
setpoint
1.0 PH01 PH02
°C
°F
CO-RH
Used only if
PG06 = 2
Pr02
Anti-freeze temperature minimum
differential
2.0
0.0
0.0
20.0
36.0
°C
°F
CO-RH
Pr03
Recovery heat exchanger by-pass cycle
time for cyclical defrosting
5 1 99 Min CO-RH
ALARM PARAMETERS
PA03
Enabling of supply/return fans thermal
overload alarm
Active
(1)
Not-active
(0)
Active (1) - CO-S