EVCO S.p.A. c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104
EVCO
page 42 of 68
6. REGULATIONS
6.1 State of the unit
There are several unit switch-on/off procedures:
1) Via the relevant ON/OFF key
Switch-ON: press the relevant key for about 2 seconds, if all the conditions are fulfilled the unit starts working
(“ON” mode).
Switch-OFF: press the relevant key for about 2 seconds, the unit stops working (“OFF” mode).
2) Using the Start/Stop from digital input control (parameter, PH05=1)
Switch-ON: close the contact, if all the conditions are fulfilled the unit starts working (“ON” mode).
Switch-OFF: if the contact is open the unit stops working (“OFF from Start/Stop” mode).
3) Via Supervision protocol (parameter, PH06=1)
Switch-ON: activate the switch-on state from protocol, if all the conditions are fulfilled the unit starts working
(“ON” mode).
Switch-OFF: if deactivated by switch-on state protocol the unit stops working (“OFF from Supervisor” mode).
The ON/OFF status from key has priority with respect to the other two. In fact the ON/OFF states by digital input and
supervision protocol can only be reached with machine in “ON” mode.
A machine switched-off by Start/Stop digital input can:
pass to the OFF state from key (by pressing ESC).
pass to the OFF state from supervisor if the OFF condition from digital input returns and the OFF state is set
by supervisor.
ass to the ON state if the ON condition from digital input returns and the OFF state is not set by supervisor.
A unit switched-OFF by supervision protocol can:
Move to the OFF state by key (by pressing ESC key).
Move to the OFF state from digital input if the OFF condition from supervisor ceases and the OFF state from
digital input is triggered.
Move to the ON state if the OFF condition from supervisor ceases and the OFF state is not present from digital
input.
The unit ON/OFF key is the ESC key pressed for about 2 seconds.
The remote Start/Stop input (when present) can be configured using the parameters:
- PH05: Enables the function
- PH52: Sets the NC, NO logic for the digital contact