C-PRO MICRO SAVE APPLICATION MANUAL
Page 15
2.4 Connection lay out for C-PRO EXP MICRO CAN
Below find the connection lay out of the expansion with tables relevant to the meaning of the inputs
and outputs.
Connector 1: Connection for the relay outputs
Conn. Code Description
C1-1 DO1 Relay n.1 normally open contact
C1-2 COMMON DO1 Common relay n.1
C1-3 DO2 Relay n.2 normally open contact
C1-4 COMMON DO2 Common relay n.2
C1-5 DO3 Relay n.3 normally open contact
C1-6 COMMON DO3 Common relay n.3
C1-7 DO4 Relay n.4 normally open contact
C1-8 COMMON DO4,
DO5
Common relay n.4, 5
C1-9 DO5 Relay n.5 normally open contact
C1-11 DO6 Relay n.6 normally open contact
C1-12 COMMON DO6 Common relay n.6
Connector 2: Connector for low voltage signals
Conn. Code Description
C2-1 12VAC Power supply (12VAC/DC)
C2-2 Not connected Not connected
C2-3 GND Common analogue and digital inputs
C2-4 GND Common analogue and digital inputs
C2-5 AI4 Analogue input n.4 (for NTC 0/4-20 mA or 0-5V transducers)
C2-6 AI3 Analogue input n.3 (for NTC 0/4-20 mA or 0-5V transducers)
C2-7 AI2 Analogue input n.2 (for NTC probes)
C2-8 AI1 Analogue input n.1 (for NTC probes)
C2-9 12VAC Power supply (12VAC/DC)
C2-10 12VDC 0/4-20 mA transducers and phase cut module power supply
(max. 50 mA, not protected against short circuit)
C2-11 AO1 Jog output for phase cut module
C2-12 DI5 Digital input n.5
C2-13 DI4 Digital input n.4
C2-14 DI3 Digital input n.3
C2-15 DI2 Digital input n.2
C2-16 DI1 Digital input n.1
Connector 3: Connector for the controller (IntraBus)
Conn. Code Description
C3-1 12VDC Power supply
C3-2 GND Common
C3-3 DATA Serial live
Connector 3: Connector for the controller (CAN)
Conn. Code Description
C3-1 CAN + Connector for the connection of the CAN + serial port
C3-2 GND Mass reference connector
C3-3 CAN - Connector for the connection of the CAN - serial port