C-PRO MICRO SAVE APPLICATION MANUAL
Page 27
Code Parameter description Default Min Max UM Menu Notes
ALARM PARAMETERS
PA03
Enabling of supply/return fans thermal
overload alarm
Active (1)
Not-active
(0)
Active (1) - CO-S
PA05
Enabling of differential pressure switch
alarm
Not-active
(0)
Not-active
(0)
Active (1) Sec CO-S
PA06 Delay of differential pressure switch alarm 10 0 999 Sec CO-S
PA08
Signals differential pressure switch alarm
on alarm relay
No (0) No (0) Yes (1) Sec CO-S
Only if
PG02=0
PA09 Anti-freeze alarm active on hot water coil
Not-active
(0)
Not-active
(0)
Active (1) Sec CO-S
PA10 Anti-freeze alarm delay on hot water coil 10 0 999 Sec CO-S
PA12 Activates the heaters thermal switch alarm
Not-active
(0)
Not-active
(0)
Active (1) Sec CO-S
Only if
PG02=1
PA13
Signals heaters thermal overload alarm on
alarm relay
No (1) No (0) Yes (1) CO-S
Only if
PG02=1
PA16
Enable supply high temperature alarm
from temperature probe
Not-active
(0)
Not-active
(0)
Active (1) CO-S
PA17 Supply high temperature alarm setpoint 85.0 PH01 PH02
°C
°F
CO-S
PA19
Supply high/low temperature alarms
differential
3.0
0.0
0.0
20.0
36.0
°C
°F
CO-S
PA20 High/low temperature alarms delay 10 0 999 Sec CO-S
PA22 Expansion alarm delay 5 0 999 Sec CO-S
PA24 RTC alarm enabling Active (1)
Not-active
(0)
Active (1) - CO-S
PA26 Probes alarms signals delay 10 0 240 Sec CO-S
VARIOUS PARAMETERS
PH11 Board Modbus address 1 1 247 - CO-V
PH12
Communication Baud Rate for the board
(0=1200, 1=2400, 2=4800, 3=9600,
4=19200)
3 0 4 - CO-V
PH13 ModBus Parity (0=none, 1=Odd, 2=Even) 2 0 2 - CO-V
PH14 Stop Bit ModBus (0=1bit, 1=2bit) 0 0 1 - CO-V
PH40 Enable supply temperature probe No (01) No (0) Yes (1) - CO-V
PH41 Enable return temperature probe No (0) No (0) Yes (1) - CO-V
PH42 Enable CO
2
probe (0-5V) No (0) No (0) Yes (1) - CO-V
PH43 Enable outside air temperature probe No (0) No (0) Yes (1) - CO-V
PH51 Logic of the digital input DI1 N.O. (0) N.O. (0) N.C. (1) - CO-V
PH52 Logic of the digital input DI2 N.O. (0) N.O. (0) N.C. (1) - CO-V
PH53 Logic of the digital input DI3 N.C. (1) N.O. (0) N.C. (1) - CO-V
PH54 Logic of the digital input DI4 N.C. (1) N.O. (0) N.C. (1) - CO-V
PH55 Logic of the digital input DI5 N.O. (0) N.O. (0) N.C. (1) - CO-V
PH56 Logic of the digital input DI6 N.C. (1) N.O. (0) N.C. (1) - CO-V
PH57 Logic of the digital input DI7 N.O. (0) N.O. (0) N.C. (1) - CO-V
PH58 Logic of the digital input DI8 N.C. (1) N.O. (0) N.C. (1) - CO-V
PH59 Logic of the digital input DI9 N.O. (0) N.O. (0) N.C. (1) - CO-V
PH60 Logic of the alarm relay DO10 N.O. (0) N.O. (0) N.C. (1) - CO-V
PH61 Logic of the alarm relay DO12 N.O. (0) N.O. (0) N.C. (1) - CO-V
PH80
CAN communication Baud Rate
(20K, 50K, 125K, 500K)
1 1 4 - CO-V
Note: Once the unit parameters have been configured and at each modification of the configuration parameters it is
recommended to switch OFF / switch ON the power supply to the board to make sure the configuration has been
correctly updated.