C-PRO NANO CHIL AND C-PRO MICRO CHIL – APPLICATION MANUAL
Pag. 53
2.11.2 Connection layout of C-PRO EXP MICRO
The connection layout of C-PRO EXP MICRO is shown below, with related tables explaining the
meaning of inputs and outputs.
42 3 5 76 98
2
2
1
1
3
3
1
K7 K8 K9 K10 K11 K12
16
8
15
7
14
6
13
5
12
4
11
3
10
2
9
1
connector # 2
max. 3 A
max. 3 A
max. 3 A
max. 4 A
max. 3 A
C-PRO MICROEXP
Connector 1: Connection for relay outputs
Conn. Label Description
C1-1 DO7 Normally open contact relay # 7
C1-2 COMMON DO7 Common relay # 7
C1-3 DO8 Normally open contact relay # 8
C1-4 COMMON DO8 Common relay # 8
C1-5 DO9 Normally open contact relay # 9
C1-6 COMMON DO9 Common relay # 9
C1-7 DO10 Normally open contact relay # 10
C1-8 COMMON 1 Common relays # 10, 11
C1-9 DO11 Normally open contact relay # 11
C1-10 Not in use
C1-11 DO12 Normally open contact relay # 12
C1-12 COMMON DO12 Common relay # 12
Connector 2: Connector for low-voltage signals
Conn. Label Description
C2-1 12 V AC (power
supply)
Instrument power supply (12 V AC/DC)
C2-2 Not connected Not connected
C2-3 GND Common analogue and digital inputs
C2-4 GND Common analogue and digital inputs
C2-5 AI8 Analogue input # 8 (4-20 mA transducer)
C2-6 AI7 Analogue input # 7 (4-20 mA transducer)
C2-7 AI6 Analogue input # 6 (NTC probe)
C2-8 AI5 Analogue input # 5 (NTC probe)