C-PRO NANO CHIL AND C-PRO MICRO CHIL – APPLICATION MANUAL
Pag. 79
compressor # 2. has been
enabled)
HC03
It sets the position of the digital output for
compressor # 3.
0 0 6 (12) CO-Hw
(12 if expansion
has been
enabled)
HC04
It sets the position of the digital output for
compressor # 4.
0 0 6 (12) CO-Hw
(12 if expansion
has been
enabled)
HC05
It sets the position of the digital output for
compressor # 5.
0 0 6 (12) CO-Hw
(12 if expansion
has been
enabled)
HC06
It sets the position of the digital output for
compressor # 6.
0 0 6 (12) CO-Hw
(12 if expansion
has been
enabled)
HF31
It sets the position of the analogue output of
the condensing fan in Circuit # 1.
1 0 3 (4) CO-Hw
Outputs 2 and 3
require the AO
expansion.
(4 if expansion
has been
enabled)
HF32
It sets the position of the analogue output of
the condensing fan in Circuit # 2.
0 0 3 (4) CO-Hw
Outputs 2 and 3
require the AO
expansion.
(4 if expansion
has been
enabled)
HF34
It sets the position of the analogue output
linked to the free-cooling fan output (in case it
is separated from the condensing fan).
0 0 3 (4) CO-Hw
Outputs 2 and 3
require the AO
expansion.
(4 if expansion
has been
enabled)
HP01
It sets the position of the digital output for
pump # 1 / recirculating fan.
1 0 6 (12) CO-Hw
(12 if expansion
has been
enabled)
HP02
It sets the position of the digital output for
pump # 2.
0 0 6 (12) CO-Hw
(12 if expansion
has been
enabled)
Hd01
It sets the position of the digital input for the
global ON/OFF.
0 0 6 (12) CO-Hw
(12 if expansion
has been
enabled)
Hd02
It sets the position of the digital input linked to
the secondary set point for compressor
management.
0 0 6 (12) CO-Hw
(12 if expansion
has been
enabled)
Hd05
It sets the position of the digital input linked to
the summer/winter operating mode.
0 0 6 (12) CO-Hw
(12 if expansion
has been
enabled)
Hd06
It sets the position of the digital input linked to
flow detection.
4 0 6 (12) CO-Hw
(12 if expansion
has been
enabled)
Hd07
It sets the position of the digital input linked to
the power-limiting command.
0 0 6 (12) CO-Hw
(12 if expansion
has been
enabled)
Hd09
It sets the position of the digital input linked to
the defrosting command from external contact.
0 0 6 (12) CO-Hw
(12 if expansion
has been
enabled)
Hd11
It sets the position of the digital input linked to
the first step of compressor regulation. (In
motocondensing units, compressor activation
is via DI.)
0 0 6 (12) CO-Hw
(12 if expansion
has been
enabled)
Hd12 It sets the position of the digital input linked to 0 0 6 (12) CO-Hw (12 if expansion