C-PRO NANO CHIL AND C-PRO MICRO CHIL – APPLICATION MANUAL
Pag. 8
2 Applications
Management of the following unit types is possible:
1) Air-to-air single-circuit chiller units and air-to-air single-circuit chiller units +
heat pump, using C-PRO NANO CHIL (or C-PRO MICRO CHIL).
Total number of analogue inputs: 4.
Total number of digital inputs: 5 (*).
Total number of analogue outputs: 1 + 2 optional.
Total number of digital outputs: 6.
2) Air-to-water single-circuit chiller units and air-to-water single-circuit chiller
units + heat pump, using C-PRO NANO CHIL (or C-PRO MICRO CHIL).
Total number of analogue inputs: 4.
Total number of digital inputs: 5 (*).
Total number of analogue outputs: 1 + 2 optional.
Total number of digital outputs: 6.
3) Water-to-water single-circuit chiller units and water-to-water single-circuit
chiller units + heat pump, using C-PRO NANO CHIL (or C-PRO MICRO CHIL).
Total number of analogue inputs: 4.
Total number of digital inputs: 5 (*).
Total number of analogue outputs: 1 + 2 optional.
Total number of digital outputs: 6.
4) Single-circuit motocondensing air-based units and single-circuit
motocondensing air-based units with cycle inversion, using C-PRO NANO CHIL (or C-PRO
MICRO CHIL).
Total number of analogue inputs: 4.
Total number of digital inputs: 5 (*).
Total number of analogue outputs: 1 + 2 optional.
Total number of digital outputs: 6.
5) Single-circuit motocondensing water-based units and single-circuit
motocondensing water-based units with cycle inversion, using C-PRO NANO CHIL (or C-PRO
MICRO CHIL).
Total number of analogue inputs: 4.
Total number of digital inputs: 5.
Total number of analogue outputs: 1 + 2 optional.
Total number of digital outputs: 6.
(*) Note: The total number of digital inputs is 6, if analogue input AI04 is used as additional digital
input (parameter PH44).
6) Air-to-air single-circuit chiller units and air-to-air single-circuit chiller units +
heat pump, using C-PRO NANO CHIL (or C-PRO MICRO CHIL) and C-PRO EXP
MICRO.
Total number of analogue inputs: 8.
Total number of digital inputs: 10 (*).
Total number of analogue outputs: 2 + 2 optional.
Total number of digital outputs: 12.