C-PRO NANO CHIL AND C-PRO MICRO CHIL – APPLICATION MANUAL
Pag. 74
PP07
Shutdown of pump / recirculating fan during
defrosting
No (1) No (0) Yes (1) IS-P
PP08
Difference in operating hours between the two
pumps, requiring their being swapped.
4 1 240 Hours IS-P
PP09
Pump operating time at low water flow (flow
alarm)
15 0 999 Sec. IS-P
PP10
Pump operating time at low temperature of
outflow water (anti-frost alarm)
15 0 999 Sec. IS-P
PP11 Hot start enabling of recirculating fan Yes (1)
No (0) Yes (1) - IS-P
PP12 Hot start set point of recirculating fan 36.0 0.0 70.0 °C IS-P
PP13 Hot start differential of recirculating fan 4.0 0.1 10.0 °C IS-P
ANTI-FROST PARAMETERS
Pr01 Enabling of anti-frost heating elements Yes (1)
No (0) Yes (1) IS-AF
Pr02 Anti-frost heating element set point 5.0 Pr11 10.0 °C IS-AF
Pr03 Anti-frost heating element differential 2.0 0.1 10.0 °C IS-AF
Pr04
Forcing of anti-frost heating elements with
probe error
No (0)
No (0) Yes (1) IS-AF
Pr11 Anti-frost alarm threshold 3.0 -30.0 Pr01 °C IS-AF
Pr12 Anti-frost alarm differential 2.0 0.1 10.0 °C IS-AF
FREE-COOLING PARAMETERS
PS01 Enabling of free-cooling No (0)
No (0) Yes (1) IS-FC
PS02 Shutter modulation band 3.0 0.1 20.0 °C IS-FC
PS03 Fan minimum speed 0.0 0.0 PS04 % IS-FC
PS04 Fan maximum speed 100.0 PS03 100.0 % IS-FC
PS11
W/Temp-A/Temp differential for free-cooling
activation
3.0
2.0
9.9
°C IS-FC
PS13
W/Temp-A/Temp hysteresis for free-cooling
activation
2.0 0.5 5.0 °C IS-FC
PS14 Free-cooling activation min. time 30 0 240 Sec. IS-FC
PS15 ON/OFF valve hysteresis 0.5 0.1 5.0 °C IS-FC
PS16
Max. threshold for motor-operated valve
opening
2.0 0.1 PS02 °C IS-FC
PS21
Enabling of free-cooling when compressors
are ON
Yes (1)
No (0) Yes (1) IS-FC
ALARM PARAMETERS
PA01 Flow alarm delay from machine start-up 10 1 999 Sec. IS-S
PA02
Flow alarm by-pass time during normal
operation
1 1 999 Sec. IS-S
PA03
Number of triggered flow alarms with auto-
reset before the alarm becomes manual
3 0 9 IS-S
PA04 Delay interval for notification of probe error 10 0 240 Sec. IS-S
PA05
High-temperature alarm threshold during
summer operation (chiller)
30.0 10.0 40.0 °C IS-S
PA06
Low-temperature alarm threshold during
winter operation (heat pump)
15.0 10.0 40.0 °C IS-S
PA07 Triggering delay for temperature alarm 30 1 999 Sec. IS-S
PA08
Consequent time for a temperature alarm:
0 = Notification only
1 = Machine stop
0 0 1 Sec. IS-S
PA09 Reset differential for temperature alarm 0.5 0.1 10.0 °C IS-S
PA10
Temperature alarm inhibition interval from
system start-up
15 0 999 Sec. IS-S
PA11
Low-pressure alarm threshold during winter
operation (heat pump)
3.0 0.1 9.9 Bar IS-S
PA12
Low-pressure alarm reset differential during
winter operation (heat pump)
1.0 0.1 4.0 Bar IS-S
PA13
Low-pressure alarm by-pass interval from
start-up of first compressor
120 0 999 Sec. IS-S
PA14
Number of triggered low-pressure alarms with
auto-reset before the alarm becomes manual
3 0 5 IS-S